I-o-display-systems Basic I/O Product Manual do Utilizador Página 56

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 81
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 55
Installation 2
2-2(Vol.2)
Power Wiring:
Power connections are made at the 2 position terminal block located on the module board
marked +5V and GND No. 8 captive wire clamps accept 10-16 AWG wire or spade lugs.
Power wiring conventions:
+ of the power source to the terminal marked +5V
- of the power source to the terminal marked GND
Power requirements
Voltage: 5.0- 5.4Vdc
Current: 250 mA + 25mA per digital module and 200mA per analog module.
Practices: In general it is good practice to reserve the +5Vdc power supply
exclusively for the task of powering one or more BASIC I/O ADs. As
with any microprocessor based equipment, reasonably clean power is
required for reliable operation. Sharing power with other devices such as
field signal transducers and contact excitation should be avoided
Vista de página 55
1 2 ... 51 52 53 54 55 56 57 58 59 60 61 ... 80 81

Comentários a estes Manuais

Sem comentários